Fire testing scope

Rockwool have undertaken a rigorous fire resistance testing program for use of Ablative Coated Batt in penetration seal applications. This program examined the fire resistance performance of Ablative Coated Batt when used for sealing penetrations in different wall constructions, and with a wide variety of penetrations – plastic pipes, metal pipes, cables & ducts. All tests were conducted at UKAS accredited fire test laboratories to BSEN 1366-3: 2006 standard.

The tables below show likely performance in fire stopping services in various sized apertures within different wall constructions:



Wall type - 120 minute flexible lightweight partition

Aperture size 1200 x 600 1200 x 12002400 x 24002400 x 2880
insulationintegrity insulation integrity insulation integrityinsulationintegrity
Plastic pipes (ABS, PP, HDPE)120 60 9060  120606060
Copper & Steel pipes120 60 9060 12060 6060
Cables120 60 9060 12060 60 60 
Steel ducts120 n/a 9060 120 n/a 60n/a 
 

Wall type - 120 minute 150mm concrete blockwork wall

Aperture size 1200 x 600 1200 x 12002400 x 24002400 x 2880
insulationintegrity insulation integrity insulation integrityinsulationintegrity
Plastic pipes (ABS, PP, HDPE)120 60 9060  120606060
Copper & Steel pipes120 60 9060 12060 6060
Cables120 60 9060 12060 60 60 
Steel ducts120 n/a 9060 120 n/a 60n/a 



Wall type - 240 minute 150mm concrete blockwork wall

Aperture size 1200 x 600 1200 x 12002400 x 24002400 x 2880
insulationintegrity insulation integrity insulation integrityinsulationintegrity
Copper & Steel pipes240120 9060 12060 6060
Cables240120 9060 12060 60 60 





Wall type - 240 minute 215mm masonry wall

Aperture size 1200 x 600 1200 x 1200
insulationintegrity insulation integrity
Copper & Steel pipes2401809060



Floor type - 240 minute 150mm concrete floor

Aperture size 1200 x 600
insulationinsulation 
Copper & Steel pipes240120
Cables24060



As part of the system solution Rockwool Acoustic Intumescent Sealant, Insulated Fire Sleeve, FireTube and Conlit Bandage were used to seal various blank seal, pipe and cable penetrations in these tests. All tests were conducted at UKAS accredited fire test laboratories to BSEN 1366-3: 2006 standard.

Given the range of tests, an assessment of scope has been produced by Chiltern International Fire Ltd. This Assessment gives details of the Tested and Approved configurations of penetration sealing systems fitted within a Rockwool Ablative Coated Batt sealing system. A copy of this assessment is available on request from Technical Support; however it is worth noting that Rockwool has a continuous improvement policy for product development. It is recommended to check on www.rockwool.co.uk from time to time or the most up-to-date copy of the assessment

Technical Support

For further information on dedicated Fire stopping solutions, contact Rockwool Technical Support on +44(0) 871 222 0011

Technical manual download

Register to gain access to the Fire Stopping technical manual, Rockwool's complete guide to penetration sealing.

Visit download page

Print Share